Rated mechanical endurance is 30 million operations, with contact reliability of one incorrect switching per 100 million at 17 V, 1 mA. The IP20 front protection suits enclosed control panels; pollution degree 3 covers industrial environments with conductive pollution.
For switching loads, the contact ratings vary by voltage: 10 A at 24 V, 6 A at 230 V, 3 A at 400 V, 2 A at 500 V, and 1 A at 690 V. The 6 kV surge voltage resistance ensures coordination with upstream surge protection in industrial panels. Terminals accept solid conductors: 2x 0.5–1.5 mm², 2x 0.75–2.5 mm², and 2x 4 mm² (or AWG equivalents 2x 20–16, 2x 18–14, 1x 12). The clamping range covers most control wiring gauges used in panel builds. Depth is 72 mm, width 45 mm, height 57.5 mm — compact enough for dense DIN-rail layouts.
Fastening is screw or snap-on onto a DIN rail — no adapter needed. The size S00 body fits standard 45 mm wide slots. Shock resistance rated 10g / 5 ms and 5g / 10 ms.