Coil holds at 3.2 W DC; the magnet circuit is rated for 30 V rated value with a 0.8 initial pickup threshold and 1.1 full-scale dropout.
Contact configuration and ratings
Switching current by voltage: 10 A at 24 V, 6 A at 230 V, 3 A at 400 V, 2 A at 500 V, 1 A at 690 V, and 0.27 A at 220 V. The 110 V rating is 1 A. These are the rated operational currents — use them for contactor coil switching, indicator lamps, or small solenoid valves within the S00 frame's thermal limits.
Shock resistance rated at 10g for 5 ms and 5g for 10 ms — sufficient for most industrial panel applications but not for high-vibration environments like direct engine mounting. Pollution degree 3, meaning it tolerates conductive pollution in controlled environments. Terminal capacity accepts 2x 0.5 to 1.5 mm² solid, 2x 0.75 to 2.5 mm², or 2x 4 mm². Surge voltage resistance rated at 6 kV.