It carries four normally-open instantaneous contacts rated for a range of voltages: 10 A at 24 V, 6 A at 230 V, 3 A at 400 V, 2 A at 500 V, and 1 A at 690 V. The 24 VDC coil draws 1.4 W both during pickup and hold, with a pickup threshold of 0.85 x rated voltage and a dropout threshold of 0.15 x rated voltage. A built-in varistor suppresses coil surge transients.
The 45 mm wide, 60 mm tall, 73 mm deep footprint fits standard S00 panel layouts.
Environmental and endurance ratings
Rated for pollution degree 3 (conductive or dry non-conductive pollution). Shock resistance is 10g / 5 ms and 5g / 10 ms. Mechanical life is typical 30 million operations.