It carries six instantaneous normally-open contacts — no delayed, make-before-break, or auxiliary-switch variants on this order code. The 10 A rating at 24 V (AC/DC) covers typical PLC and relay coil loads; at 230 V the rating drops to 6 A, and at 400 V to 3 A, reflecting the derating for higher-voltage switching. The coil holding power at DC is 3.2 W, which is relevant for sizing the control transformer and ensuring the DC supply can sustain multiple contactors in held-in state.
Side clearance to adjacent devices is zero — no spacing gap required.
Terminals accept solid conductors: 2x 0.5–1.5 mm², 2x 0.75–2.5 mm², and 2x 4 mm². Shock resistance is 10g / 5 ms and 5g / 10 ms — sufficient for most industrial machinery but not for high-g mobile applications.