It carries six instantaneous normally-open (NO) contacts, rated for switching control circuits and signal loads up to 10 A in AC-12 duty. The front face carries IP20 finger protection; the rest of the enclosure is open to the panel environment, so install it inside a cabinet with a door.
The coil is rated 230 V AC at both 50 Hz and 60 Hz, with an operating range of 0.8...1.1 × rated voltage at 50 Hz and 0.85...1.1 at 60 Hz — meaning the coil will pick up reliably as low as 184 V at 50 Hz and 195.5 V at 60 Hz, and hold in through a 10% overvoltage. Contact ratings are given per voltage class: 10 A at 24 V, 6 A at 230 V, 3 A at 400 V, 2 A at 500 V, and 1 A at 690 V. These are the thermal continuous currents the contacts can carry in AC-12 (resistive control) service. For inductive loads or DC switching, derate per the manufacturer's curves — the 690 V / 1 A rating gives a sense of the arc-quenching limit at higher voltages. The six contacts are all instantaneous (no delayed, leading, lagging, or make-before-break variants) — they close and open together with the armature.
Environmental and installation limits
Shock resistance is 10 g / 5 ms and 5 g / 10 ms, adequate for most rotating machinery and conveyor applications but not rated for high-g impact environments. Terminals accept solid conductors from 0.25 to 2.5 mm² (2 × that range per clamp).