It's built on the S00 frame size, the smallest in the SIRIUS family, which keeps the panel footprint tight at 45 mm wide. That steady draw matters when you're sharing a power supply across a row of contactors in a panel. That means you're not fighting panel layout constraints — it'll work in tight enclosures or angled subpanels.
Each of the six NO contacts is rated 10 A at 24 V, 6 A at 230 V, 3 A at 400 V, and 1 A at 690 V. These are thermal continuous ratings (AC-1 / resistive load class) — so they tell you the maximum current the contacts can carry without overheating when switching resistive loads like heaters or signal lamps. For motor or inductive loads, you'd derate per the AC-3 curve, but the 10 A at 24 V gives you headroom for pilot-duty circuits.
Wiring and panel integration
Terminals accept solid conductors from 0.25 to 2.5 mm² — that covers standard control wiring from 24 AWG up to 14 AWG. The screw-clamp terminals are reliable for panel builders who prefer a positive mechanical connection over push-in terminations.