It provides four normally-open instantaneous contacts rated for 10 A thermal current at 24 V, 6 A at 230 V, and 3 A at 400 V. That 10 A figure governs the continuous current each contact can carry in a control panel; the lower values at higher voltages reflect the switching arc limits for AC loads. The 6 kV surge voltage resistance means it holds off transient spikes common in industrial panels without flashover.
The 45 mm width and 57.5 mm height match the S00 footprint; depth is 111 mm.
Wiring and environmental limits
Shock resistance is rated at 10g for 5 ms and 5g for 10 ms, adequate for most machinery applications but not extreme vibration environments. The contact reliability spec — one incorrect switching operation per 100 million cycles at 17 V, 1 mA — indicates the contacts are silver-alloy and suitable for low-level logic signals, not just power switching.