This is the part for extending control-circuit contact density on a contactor or relay base — it mirrors the main contactor's coil state to additional signal paths. Rated for 10 A at 24 V, 6 A at 230 V, and 1 A at 690 V, the contact ratings cover the typical control-voltage range found in IEC panels. The 4 NO arrangement gives you four independent make contacts that close when the coil picks up — no overlap with NC or changeover contacts on this variant.
Mounts via screw and snap-on to DIN rail. Terminals accept 2x solid conductors from 0.25 to 2.5 mm². Depth is 114 mm, height 60 mm — check clearance to the gland plate if the panel is shallow.
RoHS compliance date is 01.07.2006, covering the EU RoHS directive.
Contact reliability and operating conditions
Shock resistance is 10g / 5 ms and 5g / 10 ms. Pollution degree 3, meaning it tolerates conductive pollution in industrial environments where occasional condensation occurs.