It is designed for control-circuit switching in motor starter and contactor assemblies, providing feedback or interlock signals without the timing complexity of delayed-contact variants. Rated switching currents span 10 A at 24 V, 6 A at 230 V, 3 A at 400 V, 2 A at 500 V, and 1 A at 690 V — covering the typical control-voltage range for industrial panels. Mechanical life is rated at 10 million operations typical, and the part withstands surge voltages up to 6 kV, pollution degree 3, and shock loads of 10 g for 5 ms and 5 g for 10 ms.
Dimensions are 45 mm wide, 60 mm high, and 114 mm deep. Solid-wire capacity is 2 x (0.25 to 2.5 mm²), accepting standard control-circuit conductors with or without ferrules.