Rated 10 A at 24 V (AC-12) and 6 A at 230 V, the contact rating drops with voltage: 3 A at 400 V, 2 A at 500 V, 1 A at 690 V. That derating curve matters if you're switching a mix of control voltages on the same contactor — the 690 V figure governs the worst-case thermal limit. Coil hold power is a constant 3.2 W DC, so the thermal budget inside a crowded enclosure is predictable.
Mounts via screw or snap-on to DIN rail. Width is 45 mm, depth 114 mm, height 60 mm. Side clearance to adjacent devices is 0 mm — it can be ganged without spacing, which saves rail real estate. Front protection is IP20 — safe for finger contact inside an enclosure but not for washdown or dust.
Wiring and terminal data
Solid conductor capacity is 2x (0.25... 2.5 mm²) per terminal. The coil is rated 24 VDC with a closing and holding power of 3.2 W. No auxiliary switch built in — this is a bare contactor block for external wiring.