Panel fit and contact configuration
It carries six normally-open (NO) instantaneous contacts and zero NC, make-before-break, or delayed-switching contacts — so it functions purely as a signal multiplier or interposing relay bank, not a sequencing element. The 114 mm depth fits standard enclosures; the 60 mm height leaves room for a second tier of terminals above a busbar trunk.
The coil is rated 48 V DC, with a closing and holding power of 3.2 W — a continuous-duty magnet that stays cool enough for dense panel layouts but draws enough to need a properly sized DC supply (a 24 V supply won't pull it in). Contact ratings are given for AC-12 duty (resistive loads, control circuits): 10 A at 24 V, 6 A at 230 V, 3 A at 400 V, 2 A at 500 V, and 1 A at 690 V. These are the maximum continuous currents the contacts can make and carry — not motor-switching (AC-3) figures, so size this for signal-level or small resistive loads only.
Environmental and compliance data
Shock resistance is 10g / 5 ms and 5g / 10 ms, and the mounting position allows ±180° rotation on a vertical surface plus ±22.5° tilt forward/backward — flexible for tight enclosures or angled subpanels. Terminals accept solid or stranded conductors from 0.25 to 2.5 mm² (2x per clamp), which covers standard control wiring up to 14 AWG. Substance prohibitance date is July 1, 2006 — consistent with RoHS compliance; the part carries no product extension auxiliary switch option.