It carries a rated operating current of 10 A at AC-12 (resistive load), which is the rating that governs its use in control transformers, PLC outputs, and relay coils — not a motor-switching figure. The contact configuration is 2 normally open instantaneous contacts, with no delayed or lagging switching, so it's a straight signal repeater for the main contactor's state.
Mounts via screw or snap-on onto DIN rail, with the S00 footprint (90 mm wide, 57.5 mm high, 72 mm deep) leaving room for a full starter stack in a standard panel.
Mechanical endurance and environmental range
Rated for 5,000,000 mechanical cycles typical for SIRIUS auxiliary contactors in this frame.
Wiring and terminal capacity
Terminals accept solid conductors: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), and 2x 4 mm². That covers standard control wiring (1.5 mm² for signal loops, 2.5 mm² for short power feeds) without needing ferrule adapters.