It provides 2 normally-open and 2 normally-closed instantaneous contacts — no leading, lagging, or delayed switching — so it's a straight four-pole auxiliary block for feedback, interlock, or pilot-duty loops. Rated for 10 A at 24 V, 6 A at 230 V, and 3 A at 400 V, with a 690 V rated value of 1 A. Contact reliability is one incorrect switching operation per 100 million cycles at 17 V, 1 mA — effectively dry-circuit capable for low-energy signals like PLC inputs or status LEDs.
Dimensions: 57.5 mm high, 90 mm wide, 72 mm deep. That 72 mm depth is the key number for panel clearance — it sits flush with the contactor body, not protruding past the coil terminals.
Environmental and electrical ratings
Shock resistance 10g for 5 ms and 5g for 10 ms — adequate for machine-mounted panels on conveyors or compressors. Surge voltage resistance rated at 6 kV, which covers overvoltage category III in 400 V systems — the contactor's insulation coordination is built for direct connection to the mains side of a control transformer.
RoHS compliance date of July 1, 2006 is on record, confirming the part meets EU substance restrictions for current builds.