It uses screw-type terminals and is rated for a maximum thermal current of 10 A, with specific contact ratings across AC and DC voltages.
Contact Ratings and Application
This block carries a rated operational current of 10 A at 24 V, 6 A at 230 V, and 3 A at 400 V under AC-15 duty, which covers switching of electromagnetic loads like contactor coils. For DC switching, the ratings are 10 A at 24 V, 4.7 A at 60 V, and 0.26 A at 600 V.
The block snaps onto the front of S00 contactors and contactor relays. Dimensions are 28.5 mm wide, 37.5 mm high, and 41.5 mm deep. Wiring accepts 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²) with core-end processing, or 2x (20 to 16) and 2x (18 to 14) AWG.