S00 frame, DIN-rail mount
S00 frame size — 73 mm deep, 45 mm wide, 70 mm tall. That covers the odd panel angles you get in locomotive cabinets or wayside enclosures.
DC switching and timing
DC switching current is rated per voltage step: 10 A at 24 V, 4.7 A at 60 V, 3 A at 110 V, 1.2 A at 220 V, 0.5 A at 440 V, 0.26 A at 600 V, and 1 A at 690 V. The magnet coil draws 4.5 W to close and holds at 0.75 W — the holding power is low enough that a 24 VDC supply with modest current capacity can keep it sealed without overheating.
Current production — no phase-out notice. The contactor relay carries a mechanical life of 30 million typical operations. RoHS compliance date is 2009-10-01.