Skip to main content
Siemens 3RH2131-1AN60 — Contactors

Siemens 3RH2131-1AN60 SIRIUS Auxiliary Contactor

MPN3RH2131-1AN60
Active

Siemens SIRIUS 3RH2131-1AN60 auxiliary contactor, size S00, 3 NO instantaneous contacts, 10 A at 230 V, screw and snap-on mounting on 35 mm DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RH2131-1AN60 — Identification
ParameterValue
Contactor frame sizeS00
3RH2131-1AN60 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V10 A
Rated value @ 24 V10 A
Rated value @ 60 V4.7 A
Rated value @ 110 V3 A
Rated value @ 220 V1.2 A
3RH2131-1AN60 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.8 ... 1.1
Rated value @ 50 Hz200 V
3RH2131-1AN60 — Contacts & Poles
ParameterValue
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RH2131-1AN60 — Connection & Mounting
ParameterValue
Conductor cross-section, solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail
3RH2131-1AN60 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RH2131-1AN60 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RH2131-1AN60 — Mechanical
ParameterValue
Width45 mm
Height57.5 mm
Depth73 mm
3RH2131-1AN60 — Specifications
ParameterValue
At AC4 ... 15 ms

Product details

The Siemens 3RH2131-1AN60 is a SIRIUS auxiliary contactor in frame size S00, carrying three normally-open instantaneous contacts. Mechanical endurance is listed at 30,000,000 operating cycles typical, which reflects the S00 frame's duty in high-cycle signalling and interlocking applications rather than main power switching.

Panel fit and mounting envelope

These are the minimum air gaps to adjacent metalwork or other devices for the rated insulation voltage — a panel layout that pinches these clearances risks flashover at pollution degree 3.

Rated operational current across the voltage range

The steep derating above 400 V reflects the arc extinction limits of the S00 air-break contact system.

Pollution degree 3 means the contactor is rated for conductive pollution environments typical of industrial control panels without a sealed enclosure. The part carries a RoHS compliance substance prohibition date of 10/01/2009, confirming it meets the original RoHS directive. Relative humidity minimum is 10 % — no upper humidity limit is listed in this record, so the storage envelope should be treated as the standard IEC 60068-2-30 damp-heat cyclic profile unless the full datasheet specifies otherwise.

Frequently asked questions

How can I get pricing and availability for 3RH2131-1AN60?

The 3RH2131-1AN60 is sourced to order through independent distribution. Submit an RFQ for current pricing and availability — the quote will reflect the BOM quantity and confirmed lead time at that point.

What compliance documentation does Siemens provide for 3RH2131-1AN60?

The part carries a RoHS compliance date of 10/01/2009, confirming it meets the original RoHS directive.

MPN
3RH2131-1AN60