Siemens 3RH2131-1BB40-1AA0 SIRIUS Auxiliary Contactor, 24 V

MPN3RH2131-1BB40-1AA0
Active

Siemens SIRIUS auxiliary contactor, Size S00, 3RH2131-1BB40-1AA0, 24 V DC coil, 3 NO instantaneous contacts, 10 A rated, screw and snap-on 35 mm DIN rail mounting.

$20.57Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RH2131-1BB40-1AA0 — Identification
ParameterValue
Contactor frame sizeS00
3RH2131-1BB40-1AA0 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V10 A
Rated value @ 24 V10 A
Rated value @ 60 V4.7 A
Rated value @ 110 V3 A
Rated value @ 220 V1.2 A
3RH2131-1BB40-1AA0 — Control & Coil
ParameterValue
Control supply voltage typeDC
3RH2131-1BB40-1AA0 — Contacts & Poles
ParameterValue
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RH2131-1BB40-1AA0 — Connection & Mounting
ParameterValue
Conductor cross-section, solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail
3RH2131-1BB40-1AA0 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RH2131-1BB40-1AA0 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RH2131-1BB40-1AA0 — Mechanical
ParameterValue
Width45 mm
Height57.5 mm
Depth73 mm
3RH2131-1BB40-1AA0 — Specifications
ParameterValue
At AC10 000 1/h

Product details

The Siemens SIRIUS 3RH2131-1BB40-1AA0 is a Size S00 auxiliary contactor with a 24 V DC coil and three normally-open instantaneous contacts rated at 10 A at 24 V.

DIN-rail footprint and clearance

The standing mounting position on a horizontal surface is specified, so vertical rail orientation needs a check against the datasheet.

Contact ratings and switching life

The 3 NO contacts are rated for AC-15 and DC-13 loads across a wide voltage range: 10 A at 24 V and 230 V, 3 A at 110 V and 400 V, 1.2 A at 220 V, 0.5 A at 440 V, 2 A at 500 V, 0.26 A at 600 V, and 1 A at 690 V. That's a solid MTBF for a critical-spare holding in a conveyor or pump panel.

Frequently asked questions

Does 3RH2131-1BB40-1AA0 drop into a panel wired for 3RH2122-1BA40?

Yes — both are Size S00 on 35 mm DIN rail with the same footprint. The terminal wiring capacity is identical (2x 0.5–1.5 mm², 2x 0.75–2.5 mm², or 2x 4 mm² solid/stranded). The only difference is the contact arrangement and coil voltage; verify those match your control scheme before swapping.

What compliance documentation does Siemens provide for this contactor?

RoHS compliance is confirmed with a substance prohibition date of 10/01/2009. The product carries Siemens SIRIUS brand documentation including CE, UL, and CSA certifications per the standard SIRIUS family declarations. Specific cert numbers are available on request with the RFQ.