It's the part you reach for when you need to mirror a contactor's state or interlock a sequence — no coil load switching, just signal-level circuit extension on a DIN rail.
Fit and footprint — the DIN-rail reality
The 73 mm depth and 45 mm width put it in the standard S00 slot. That's tighter than some contactors, so if you're packing a dense panel, the 6 mm side gap is the limit you'll hit first.
Ratings that matter for the circuit
Three instantaneous NO contacts — no time delay, no auxiliary logic. Rated operational current drops as voltage climbs: 10 A at 24 V, 4.7 A at 60 V, 3 A at 110 V, 1.2 A at 220 V, 10 A at 230 V, 3 A at 400 V, 0.5 A at 440 V, 2 A at 500 V, 0.26 A at 600 V, and 1 A at 690 V. That's a steep derating curve above 400 V — if you're switching at 600 V, the 0.26 A limit means this is signal-only, not load-carrying.