Skip to main content
Siemens 3RH2131-2AP00-ZW97 — Contactors

Siemens 3RH2131-2AP00-ZW97 SIRIUS Auxiliary Contactor, S00,

MPN3RH2131-2AP00-ZW97
Active

Siemens SIRIUS auxiliary contactor, size S00, 3 NO + 1 NC instantaneous contacts, screw and snap-on 35 mm DIN rail mounting, 45 mm wide.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RH2131-2AP00-ZW97 — Identification
ParameterValue
Contactor frame sizeS00
3RH2131-2AP00-ZW97 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V10 A
Rated value @ 24 V10 A
Rated value @ 60 V4.7 A
Rated value @ 110 V3 A
Rated value @ 220 V1.2 A
3RH2131-2AP00-ZW97 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.8 ... 1.1
Rated value @ 50 Hz230 V
3RH2131-2AP00-ZW97 — Contacts & Poles
ParameterValue
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RH2131-2AP00-ZW97 — Connection & Mounting
ParameterValue
Conductor cross-section, solid or stranded2x (0,5 ... 4 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail
3RH2131-2AP00-ZW97 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RH2131-2AP00-ZW97 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RH2131-2AP00-ZW97 — Mechanical
ParameterValue
Width45 mm
Height70 mm
Depth73 mm
3RH2131-2AP00-ZW97 — Specifications
ParameterValue
At AC4 ... 15 ms

Product details

SIRIUS auxiliary contactor, size S00 — 3NO+1NC, screw terminals

The 3RH2131-2AP00-ZW97 is a Siemens SIRIUS auxiliary contactor in frame size S00, delivering 3 normally-open and 1 normally-closed instantaneous contacts. Rated operational current varies by voltage and duty: 10 A at 24 V and 230 V, 4.7 A at 60 V, 3 A at 110 V and 400 V, 1.2 A at 220 V, 0.5 A at 440 V, 2 A at 500 V, 0.26 A at 600 V, and 1 A at 690 V. These are the contact ratings — match your control voltage to the appropriate column for thermal capacity.

Snap-on mounting onto 35 mm standard mounting rail; screw terminals accept 2x (0.5 to 4 mm²) solid or stranded wire. The S00 frame size keeps the footprint compact — 45 mm wide, 70 mm high, 73 mm deep — so it fits tight DIN-rail layouts alongside contactors and overload relays. Pollution degree 3 rated, so it handles conductive dust environments common in industrial panels. Relative humidity minimum 10 %. The part is RoHS-compliant per the 10/01/2009 substance prohibition date.

For a BOM line or urgent replacement, this order code sources to a firm RFQ. No last-time-buy window to watch; the part is active and factory-supported.

Frequently asked questions

What are the key dimensions for panel layout?

Width 45 mm, height 70 mm, depth 73 mm. Requires 10 mm clearance upwards and forwards, 10 mm downwards, and 6 mm at the side.

What contact configuration does this auxiliary contactor have?

3 normally-open and 1 normally-closed instantaneous contacts. Arcing time is 10 to 15 ms at AC, with a maximum switching frequency of 10,000 operations per hour at DC.

What compliance documentation is available?

RoHS compliant per the 10/01/2009 substance prohibition date. The SIRIUS series carries IEC and UL certifications typical for industrial control gear.

MPN