It carries three normally-open instantaneous contacts rated for switching loads across a wide voltage range: 10 A at 24 V and 230 V, 3 A at 110 V and 400 V, 1.2 A at 220 V, and down to 0.26 A at 600 V. That voltage spread means it handles everything from 24 VDC PLC outputs up to 690 VAC control circuits without derating surprises.
Coil and control side
The DC coil draws 4 W during both closing and holding — no inrush spike to size your power supply around. That steady 4 W draw is the same whether the contactor is just pulled in or has been held for hours, so the thermal load on the panel is predictable. The auxiliary switch extension option means you can add more contact blocks on top if the three built-in NO contacts aren't enough for your feedback or interlock scheme.
Switching performance and mechanical life
On DC, the arcing time stretches to 7 to 13 ms — worth noting if you're switching inductive DC loads where arc extinction is slower.