Skip to main content
Siemens 3RH2131-2FB40-1AA0 — Contactors

Siemens 3RH2131-2FB40-1AA0 SIRIUS Auxiliary Contactor, 24 VD

MPN3RH2131-2FB40-1AA0
Active

Siemens SIRIUS auxiliary contactor, size S00, 3RH2131-2FB40-1AA0, 24 VDC coil, 3 NO instantaneous contacts, screw and snap-on mounting for 35 mm DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RH2131-2FB40-1AA0 — Identification
ParameterValue
Contactor frame sizeS00
3RH2131-2FB40-1AA0 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V10 A
Rated value @ 24 V10 A
Rated value @ 60 V4.7 A
Rated value @ 110 V3 A
Rated value @ 220 V1.2 A
3RH2131-2FB40-1AA0 — Control & Coil
ParameterValue
Control supply voltage typeDC
3RH2131-2FB40-1AA0 — Contacts & Poles
ParameterValue
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RH2131-2FB40-1AA0 — Connection & Mounting
ParameterValue
Conductor cross-section, solid or stranded2x (0,5 ... 4 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail
3RH2131-2FB40-1AA0 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RH2131-2FB40-1AA0 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RH2131-2FB40-1AA0 — Mechanical
ParameterValue
Width45 mm
Height70 mm
Depth73 mm
3RH2131-2FB40-1AA0 — Specifications
ParameterValue
At AC10 000 1/h

Product details

The Siemens 3RH2131-2FB40-1AA0 is a SIRIUS auxiliary contactor in size S00, carrying 3 normally open instantaneous contacts and a 24 VDC coil with an integrated diode surge suppressor. Rated operational current varies with voltage: 10 A at 24 V and 230 V, 3 A at 110 V and 400 V, 2 A at 500 V, 1 A at 690 V, 4.7 A at 60 V, 1.2 A at 220 V, 0.5 A at 440 V, and 0.26 A at 600 V. These figures define the contact load capacity across control and auxiliary circuits in different supply regimes. Mechanical endurance: 30 million cycles. Maximum switching frequency at AC: 10,000 1/h. Arcing time: 10 to 15 ms. Closing power of magnet coil at DC: 4 W.

The product carries a substance prohibition date of 10/01/2009, indicating RoHS compliance per the original directive. Pollution degree 3 suits industrial environments with conductive or dry non-conductive pollution.

Panel Fit & Integration

Dimensions: 73 mm deep, 45 mm wide, 70 mm high. The 45 mm width occupies one standard 45 mm slot on a DIN rail — important for panel fill-factor planning. The integrated diode surge suppressor on the DC coil eliminates the need for external free-wheeling diode wiring — one less component to install and verify in the panel.

Frequently asked questions

What is the depth of 3RH2131-2FB40-1AA0?

The depth is 73 mm.

What is the width of 3RH2131-2FB40-1AA0?

The width is 45 mm.

MPN
3RH2131-2FB40-1AA0