Skip to main content
Siemens 3RH2131-2WB40 — Contactors

Siemens 3RH2131-2WB40 SIRIUS Coupling Relay, 24 V DC, 10 A

MPN3RH2131-2WB40
Active

Siemens SIRIUS coupling relay, 3RH2131-2WB40, 24 V DC coil, 3 instantaneous contacts, 10 A at 24 V DC, size S00, screw and snap-on 35 mm DIN-rail mounting, with varistor surge suppression.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RH2131-2WB40 — Identification
ParameterValue
Contactor frame sizeS00
3RH2131-2WB40 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V10 A
Rated value @ 24 V10 A
Rated value @ 60 V4.7 A
Rated value @ 110 V3 A
Rated value @ 220 V1.2 A
3RH2131-2WB40 — Control & Coil
ParameterValue
Control supply voltage typeDC
3RH2131-2WB40 — Contacts & Poles
ParameterValue
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RH2131-2WB40 — Connection & Mounting
ParameterValue
Conductor cross-section, solid or stranded2x (0,5 ... 4 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail
3RH2131-2WB40 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
3RH2131-2WB40 — Environmental
ParameterValue
Operating temperature range-25 ... +50 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RH2131-2WB40 — Mechanical
ParameterValue
Width45 mm
Height70 mm
Depth73 mm
3RH2131-2WB40 — Specifications
ParameterValue
At AC10 000 1/h

Product details

Panel fit and mounting — S00 frame, dual-fix DIN rail

The 3RH2131-2WB40 is a size S00 coupling relay — the smallest frame in the Siemens SIRIUS contactor family, measuring 45 mm wide by 73 mm deep by 70 mm tall.

Switching capacity and DC voltage derating

The three instantaneous contacts (NO/NC configurable per wiring) switch at up to 10,000 operations per hour AC, with a DC switching frequency limited by the 5–20 ms contact dwell time.

Integrated surge suppression and environmental ratings

A varistor is built into the relay for coil surge suppression — no external snubber needed. The coil draws 1.6 W at DC pickup. RoHS compliance is documented with a substance prohibitance date of 10/01/2009.

MPN
3RH2131-2WB40