Coil and switching ratings
Coil rated at 24-34 VDC; the inrush peak hits 2.3 A, then the holding current settles to a mean 40 mA. The locked-rotor current peak is 0.18 A, and the arcing time runs 10-15 ms. Switching capacity varies by load voltage: 10 A at 24 V and 230 V, 4.7 A at 60 V, 3 A at 110 V and 400 V, 2 A at 500 V, 1.2 A at 220 V, 1 A at 690 V, 0.5 A at 440 V, and 0.26 A at 600 V. The at-DC operating time spans 25-45 ms. These numbers govern what loads this relay can break — match the voltage column to your circuit.
Side-by-side mounting is permitted — no gap needed between units.