The coil is rated for 24 V at both 50 Hz and 60 Hz, with an operating range of 0.8 to 1.1 times rated voltage at 50 Hz and 0.85 to 1.1 at 60 Hz — so it holds in through typical line dips but drops out cleanly below the undervoltage threshold.
The contacts carry 10 A at 24 V AC and 10 A at 230 V AC, tapering to 3 A at 400 V AC and 0.26 A at 600 V AC — these are the thermal continuous currents for general-purpose AC loads, so the same contact set handles a 24 V PLC output interposing relay or a 230 V pilot light without derating. At DC voltages the rating drops faster: 4.7 A at 60 V DC, 1.2 A at 220 V DC, 0.5 A at 440 V DC — a common gotcha for panel builders who assume AC ratings carry over to DC circuits. For a 24 V DC solenoid valve bank, the 10 A AC rating does not apply; use the DC column.
Operating temperature range is -25 to +60 °C, storage from -55 to +80 °C, with 10 % relative humidity minimum. The S00 frame dimensions — 45 mm wide, 57.5 mm tall, 73 mm deep — fit alongside a Siemens contactor in the same footprint, sharing the same DIN-rail slot pitch.
It carries the substance-prohibitance date of 10/01/2009, indicating RoHS compliance for the European market.