It's rated 10 A at both 24 V and 230 V — the same contact rating across the low-voltage control and standard line-voltage circuits, so you don't have to derate between a 24 VDC PLC output and a 230 VAC motor starter interlock.
The S00 frame is 45 mm wide and 73 mm deep — a standard slot that fits alongside a contactor or overload relay in the same rail segment.
Four instantaneous NO contacts handle resistive and lightly inductive loads. At 60 V the rating drops to 4.7 A, at 110 V to 3 A, at 220 V to 1.2 A, and at 400 V to 3 A — the curve follows the contact gap and arc-quenching design. DC switching is limited: 0.5 A at 440 V, 0.26 A at 600 V, 1 A at 690 V. Arcing time runs 10 to 15 ms; pick-up and drop-out at AC is 4 to 15 ms. Mechanical life is typical 30 million operations.