It mounts via screw or snap-on onto a standard 35 mm DIN rail, with a width of 45 mm and depth of 73 mm — a compact footprint for control-panel integration where auxiliary switching is needed alongside a main contactor.
The DC arc extinction time runs 7 to 13 ms, so the contacts clear fast enough for most PLC-driven interlock circuits. Closing and holding power of the magnet coil is 4 W DC — a steady 4 W draw that the control transformer or DC supply must budget for.
Clearance requirements: 10 mm upwards, 10 mm forwards, 10 mm downwards, and 6 mm at the side. The mounting position allows +/-180° rotation on a vertical surface and +/-22.5° tilt forward/backward — useful when fitting into a tight enclosure corner.
Operating temperature range is -25 to +60 °C; storage range is -55 to +80 °C. Pollution degree 3 (industrial environment with conductive pollution). RoHS compliance date reference is October 1, 2009. Relative humidity minimum 10%.