Skip to main content
Siemens 3RH2244-1AP60 — Contactors

Siemens 3RH2244-1AP60 SIRIUS Auxiliary Contactor, 4 NO, S00

MPN3RH2244-1AP60
Active

Siemens SIRIUS 3RH2244-1AP60 auxiliary contactor, 4 NO instantaneous contacts, size S00, screw and snap-on 35 mm DIN rail mounting, 117 mm depth, 45 mm width, 57.5 mm height.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RH2244-1AP60 — Identification
ParameterValue
Contactor frame sizeS00
3RH2244-1AP60 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V6 A
Rated value @ 24 V10 A
Rated value @ 60 V4.7 A
Rated value @ 110 V3 A
Rated value @ 220 V1.2 A
3RH2244-1AP60 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.8 ... 1.1
Rated value @ 50 Hz220 V
3RH2244-1AP60 — Contacts & Poles
ParameterValue
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RH2244-1AP60 — Connection & Mounting
ParameterValue
Conductor cross-section, solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail
3RH2244-1AP60 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
3RH2244-1AP60 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RH2244-1AP60 — Mechanical
ParameterValue
Width45 mm
Height57.5 mm
Depth117 mm
3RH2244-1AP60 — Specifications
ParameterValue
At AC4 ... 15 ms

Product details

Panel fit and contact rating for a 4 NO auxiliary block

The 3RH2244-1AP60: Depth is 117 mm, height 57.5 mm. At 690 V the switching capacity drops to 1 A — the contact gap and arc chamber limit the voltage withstand, not the current-carrying cross-section. Mechanical life is listed at 10 million operations typical, which aligns with the S00 frame's duty cycle for auxiliary switching in PLC output isolation or contactor coil control.

Ambient limits and clearance for dirty environments

The 6 mm side clearance and 10 mm clearance above/below the contactor are the minimum air gaps for PD3 with a 400 V system. This matters when the panel layout forces a non-vertical rail.

The substance prohibitance date of 10/01/2009 indicates RoHS compliance was established early; the contactor is also REACH-compliant per Siemens standard declaration.

Frequently asked questions

What is the switching capacity of 3RH2244-1AP60 at 24 V DC?

At 60 V DC the rating drops to 4.7 A, and at 110 V DC to 3 A.

What clearance does the 3RH2244-1AP60 need from other components?

These are the air and creepage distances for pollution degree 3.

MPN
3RH2244-1AP60