It is designed for control-circuit switching in motor starter assemblies, panel interlocking, and signal routing — not for main power switching. The S00 frame keeps it compact for high-density panel layouts.
The contact ratings are voltage-dependent, which is typical for DC switching. At 24 V the contacts carry 10 A; at 60 V that drops to 4.7 A, and at 110 V to 3 A. For AC-15 control-circuit duty at 230 V, the rated current is 6 A, and at 400 V it is 3 A.
RoHS compliance date is marked as 10/01/2009, and the part carries a pollution degree 3 rating (conductive pollution or dry non-conductive that becomes conductive under condensation — typical for industrial control panels).
Terminal capacity accepts 2× (0.5–1.5 mm²), 2× (0.75–2.5 mm²), or 2× 4 mm² solid or stranded wire. Clearance to adjacent devices: 10 mm upward/downward/forward, 6 mm sideways — no special derating needed at those spacing minima for standard 50/60 Hz control voltages.