Skip to main content
Siemens 3RH2271-1AP60 — Contactors

Siemens SIRIUS 3RH2271-1AP60 Auxiliary Contactor, 7 N/O, S00

MPN3RH2271-1AP60
Active

Siemens SIRIUS auxiliary contactor, size S00, 7 N/O contacts, screw and snap-on mounting onto 35 mm DIN rail, rated for 690 V AC/DC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RH2271-1AP60 — Identification
ParameterValue
Contactor frame sizeS00
3RH2271-1AP60 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V6 A
Rated value @ 24 V10 A
Rated value @ 60 V4.7 A
Rated value @ 110 V3 A
Rated value @ 220 V1.2 A
3RH2271-1AP60 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.8 ... 1.1
Rated value @ 50 Hz220 V
3RH2271-1AP60 — Contacts & Poles
ParameterValue
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RH2271-1AP60 — Connection & Mounting
ParameterValue
Conductor cross-section, solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail
3RH2271-1AP60 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
3RH2271-1AP60 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RH2271-1AP60 — Mechanical
ParameterValue
Width45 mm
Height57.5 mm
Depth117 mm
3RH2271-1AP60 — Specifications
ParameterValue
At AC4 ... 15 ms

Product details

Rated for continuous duty across a wide voltage range: 24 V at 10 A, 60 V at 4.7 A, 110 V at 3 A, 220 V at 1.2 A, 230 V at 6 A, 400 V at 3 A, 440 V at 0.5 A, 500 V at 2 A, 600 V at 0.26 A, and 690 V at 1 A. These are the thermal current ratings (Ith) at each voltage — the contactor can switch these currents in resistive or lightly inductive circuits without derating, which is the rating that governs the auxiliary circuit design, not a motor-starting curve. The arcing time sits between 10 and 15 ms at AC, and the contactor can handle up to 10 000 switching operations per hour at DC — a high duty cycle for a size S00 auxiliary block, so it suits rapid-pick applications like packaging lines or pick-and-place cells where the auxiliary contacts cycle faster than the main power contactor.

Panel Integration

Dimensions: 57.5 mm high, 45 mm wide, 117 mm deep. The width is a standard 45 mm — two 22.5 mm modules side by side — so it occupies one 45 mm slot on the DIN rail. That side clearance is tighter than the vertical; in a dense panel, leave a full 6 mm to the adjacent device to avoid arc flash tracking at pollution degree 3. Terminals accept 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or 2x 4 mm² solid or stranded wire — the larger cross-section is for daisy-chaining the common supply.

Relative humidity minimum 10 %. RoHS compliance date of 10/01/2009.

Frequently asked questions

What is 3RH2271-1AP60's listed depth?

The depth is 117 mm. Width is 45 mm, height is 57.5 mm. Side clearance required is 6 mm; vertical clearance 10 mm each direction.

MPN
3RH2271-1AP60