It is rated for a maximum of 10 A and delivers 10 A at 24 V, with AC-15 switching capability of 1 A at 690 V — enough to handle most pilot-duty and signal-level loads in a motor control center.
The 10 A maximum at 24 V covers the typical current draw of a PLC input module or a small contactor coil. The AC-15 rating of 1 A at 690 V is the key figure for switching solenoid loads in a 400–690 V panel — AC-15 is the utilization category for electromagnetic loads (contactors, relays), so this switch is rated for the inrush and inductive kick those loads produce. The snap-on mounting lets it clip directly onto the front of the contactor or relay without tools, saving DIN-rail space and keeping the wiring within the same vertical column.
Integration note
The dimensions — 36 mm wide, 37.5 mm high, 43.7 mm deep — are compact enough to fit on the front of the contactor without protruding past the mounting base. The screw terminals accept 2x (0.5…1.5 mm²) or 2x (0.75…2.5 mm²) conductors, or the AWG equivalents 2x (20…16) and 2x (18…14).