It provides 2 normally open and 2 normally closed auxiliary contacts, giving you four independent signal paths for interlocking, status feedback, or logic control. The AC coil is rated for 50/60 Hz with an operating range of 0.8...1.1 x Us at 50 Hz and 0.85...1.1 x Us at 60 Hz, so it holds in over a reasonable brownout band.
Dimensions are 45 mm wide, 57.5 mm tall, and 73 mm deep — fits the S00 slot in a modular panel layout.
The auxiliary contacts are rated for AC-12 duty at 6 A at 24 V, 3 A at 110 V, 1.2 A at 220 V, and 10 A at 230 V. These are not motor-switching currents — this is a contactor relay for signal-level and small auxiliary loads.
Coil and control supply
The coil is AC-operated with a pick-up power of 37 VA and a holding power of 5.7 VA at an inductive power factor of 0.8. That means the inrush is about 6.5x the sealed draw, so your control transformer needs to handle the momentary load when multiple contactors pick up simultaneously.
Substance prohibition date of 05/01/2012 indicates RoHS compliance per the EU directive effective from that date.