It carries 2 normally open and 2 normally closed auxiliary contacts, giving you four isolated signal paths for feedback, interlocks, or PLC inputs.
The auxiliary contacts are rated for AC-12 duty at 6 A at 24 V, 3 A at 110 V, and 1.2 A at 220 V. For higher voltages, they handle 10 A at 230 V, 3 A at 400 V, and 1 A at 690 V.
Coil and control supply
The control supply voltage is AC. Pick-up power of the magnet coil is 37 VA; holding power drops to 5.7 VA. The inductive power factor at closing is 0.8, so factor that into transformer sizing if you're driving multiple contactors from a single control transformer.