It carries 1 NC and 3 NO auxiliary contacts rated for AC-12 switching at 6 A maximum, with a 230 V rated value of 10 A. The AC coil draws 37 VA pick-up and 5.7 VA holding. Mechanical endurance is 30 million operations, and contact reliability is specified at 1 faulty switching per 100 million operations at 17 V, 1 mA — a figure that matters for PLC-level signal integrity.
Switching capability and thermal limits
Rated for 10 000 switching cycles per hour on both AC and DC loads. The AC-12 rating (6 A) governs resistive and solid-state loads.