It packs 1 NC and 3 NO auxiliary contacts, rated to handle 6 A at 24 V (AC-12) and 10 A at 230 V (AC-12). Coil consumption sits at 37 VA pick-up and 5.7 VA holding, so the control transformer sizing is modest. On a DIN rail, it occupies 45 mm width, 57.5 mm height, and 73 mm depth — a footprint that fits standard control-panel grid layouts.
Terminal wiring accepts solid or stranded: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or 2x 4 mm². For AWG, it takes 2x (20 to 16), 2x (18 to 14), or 2x 12. That range covers typical control-circuit wiring from signal loops to interposing relays.
RoHS substance prohibition applies from 05/01/2012. The contactor relay is surge-voltage rated to 6 kV, which satisfies the insulation coordination requirements of IEC 60947-1 for industrial control panels.