At 10 mm wide, it adds one normally open instantaneous contact without increasing the contactor's panel depth beyond 66 mm.
Switching capacity and contact reliability
The contact is rated for 6 A at 24 V and 230 V, with derated values across the voltage range: 2 A at 48 V and 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V and 250 V, and 3 A at 400 V. For AC-15 inductive loads at 690 V, the rated operational current is 1 A. The AC-15 ratings at lower voltages are 10 A at 24 V, 4.7 A at 60 V, 3 A at 110 V, 1.2 A at 220 V, 0.5 A at 440 V, and 0.26 A at 600 V.
Mechanical endurance and wiring
The snap-on fastening method means it clips directly onto the contactor without tools — no DIN rail or additional hardware required. Wiring accepts 2x (0.5 to 1.5 mm²) or 2x (0.75 to 2.5 mm²) solid or stranded conductors, or the equivalent AWG sizes 20-16 and 18-14. Finely stranded wire with core-end processing uses the same cross-section ranges.