Skip to main content
Siemens 3RH7140-1AH00 — Contactors

Siemens 3RH7140-1AH00 SIRIUS Contactor Relay, 4 NO, AC Coil,

MPN3RH7140-1AH00

Siemens SIRIUS contactor relay, size S00, 4 NO contacts, AC coil, screw-type terminals, 45 mm width, IP20 front.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RH7140-1AH00 — Identification
ParameterValue
Contactor frame sizeS00
3RH7140-1AH00 — Ratings & Performance
ParameterValue
Rated value @ 400 V6 A
Rated value @ 690 V1 A
Rated value @ 230 V6 A
Rated value @ 24 V6 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RH7140-1AH00 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.8 ... 1.1
Rated value @ 50 Hz48 V
3RH7140-1AH00 — Contacts & Poles
ParameterValue
Auxiliary contact reliabilityacceptability for PLC control (17 V, 5 mA)
3RH7140-1AH00 — Connection & Mounting
ParameterValue
Conductor cross-section, solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail
3RH7140-1AH00 — Environmental
ParameterValue
Operating temperature range-10 ... +55 °C
Storage temperature range-25 ... +70 °C
Installation altitude, max.2 000 m
3RH7140-1AH00 — Mechanical
ParameterValue
Width45 mm
Height57.5 mm
Depth72 mm

Product details

This is a contactor relay — it switches control circuits, not motor loads directly. The 4 NO contacts are rated for 6 A at 24 V, 230 V, and 400 V AC, and 1 A at 690 V AC, covering most 24–690 V control-voltage ranges you'd find in a panel. The contacts are also rated for PLC-level switching reliability down to 17 V, 5 mA, so it handles low-signal circuits without contact oxidation issues. The AC coil draws 27 VA pick-up and 5.4 VA holding, with a power factor of 0.8 on pick-up and 0.27 on hold — figures that matter when sizing the control transformer for a multi-contactor bank.

That covers most panel layouts without derating, but the operating temperature range is -10 to +55 °C, storage -25 to +70 °C. Screw terminals accept 2x 0.5–1.5 mm² solid/stranded, 2x 0.75–2.5 mm², or 2x 4 mm². Finely stranded wire needs ferrule processing. Rated surge voltage resistance is 8 kV, and insulation voltage is 690 V at pollution degree 3 — standard for industrial control panels operating up to 690 V line-to-line. Maximum installation altitude is 2000 m without derating.

Frequently asked questions

Will 3RH7140-1AH00 drop into a panel that was specified around 3RH6140-1AP00 without rewiring?

Both are SIRIUS contactor relays in the S00 frame with the same 45 mm width and DIN-rail mounting, so the mechanical footprint is identical. The 3RH7140-1AH00 uses screw terminals; the 3RH6140-1AP00 uses spring-cage terminals. If the panel was wired for spring-cage, you'd need to adapt the wiring method — the terminal type is the main difference.

What is 3RH7140-1AH00's listed depth (72 mm) on this component line?

The depth is 72 mm. That's the dimension from the DIN-rail mounting surface to the front of the device — relevant for enclosure depth clearance.

MPN