Skip to main content
Siemens 3RK1205-0BG00-2AA2 — Remote I/O & Fieldbus Modules

Siemens 3RK1205-0BG00-2AA2 AS-i Safety I/O Module, PL e, IP2

MPN3RK1205-0BG00-2AA2
Active

Siemens Slimline Compact I/O, AS-i SC17.5F, 2F-DI, IP20, 17.5 mm wide, spring terminals.

$114.30Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RK1205-0BG00-2AA2 — Identification
ParameterValue
Product designationSlimline Compact I/O module for use in the control cabinet
Product designAS-i SC17.5F, 2F-DI
3RK1205-0BG00-2AA2 — Communication
ParameterValue
AS-Interface supportYes
3RK1205-0BG00-2AA2 — I/O
ParameterValue
Digital inputs0
3RK1205-0BG00-2AA2 — Environmental
ParameterValue
Ingress protection (IP)IP20
Operating temperature range-25 ... +70 °C
Storage temperature range-40 ... +85 °C
Shock resistance15g / 11 ms (modules) or 10g / 11 ms (modules with device connector)
3RK1205-0BG00-2AA2 — Mechanical
ParameterValue
Width17.5 mm
Depth120 mm
Height100 mm
Mounting methodscrew and snap-on mounting

Product details

The Siemens 3RK1205-0BG00-2AA2 is a Slimline Compact I/O module for the control cabinet, designed as an AS-Interface safety slave. It carries two safety-related digital inputs (2F-DI) and uses the AS-i slave profile S-0.B.F. The module is rated for safety up to PL e per EN ISO 13849-1 and Category 4, with a safe failure fraction of 99% and a PFHd of 4.5E-9 1/h for high-demand applications. It operates on the AS-Interface bus voltage range of 18 to 31.6 V and supports AS-i Power24V.

Panel fit and field wiring

This module is 17.5 mm wide, 100 mm high, and 120 mm deep — a single slice on a DIN rail. Mounting is screw and snap-on, so it clips into place without tools. The IP20 rating means it lives inside a cabinet, not on the line floor. Connections are spring-loaded terminals accepting 0.5 to 1.5 mm² solid or stranded wire (AWG 20–16), or 0.25 to 1.0 mm² finely stranded with ferrules. The ID1 code is factory-set to F and changeable via the front addressing socket. Yellow LEDs show input/output status.

Frequently asked questions

What safety level does this module achieve?

It is rated for PL e per EN ISO 13849-1, Category 4, with a safe failure fraction of 99% and a PFHd of 4.5E-9 1/h for high-demand operation.

What is the operating voltage range?

It operates on the AS-Interface bus voltage from 18 to 31.6 V and supports AS-i Power24V.

How is it wired and mounted?

Mounting is screw and snap-on on a DIN rail. Connections use spring-loaded terminals accepting 0.5 to 1.5 mm² solid or stranded wire, or 0.25 to 1.0 mm² finely stranded with ferrules.

MPN
3RK1205-0BG00-2AA2