Skip to main content
Siemens 3RK1301-0BB20-0AB4 — Remote I/O & Fieldbus Modules

Siemens SIMATIC 3RK1301-0BB20-0AB4 Motor Starter, 24 V DC, 5

MPN3RK1301-0BB20-0AB4

Siemens SIMATIC motor starter, direct starter, 24 V DC, CLASS 10 and 10A adjustable trip, 50 kA at 400 V, PROFINET and PROFIBUS DP, order code 3RK1301-0BB20-0AB4.

$590.55Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RK1301-0BB20-0AB4 — Identification
ParameterValue
Product designationMotor starters
Product designdirect starter
3RK1301-0BB20-0AB4 — Communication
ParameterValue
PROFIBUS DP supportYes
PROFINET supportYes
AS-Interface supportNo
Bus communicationYes
3RK1301-0BB20-0AB4 — I/O
ParameterValue
Digital inputs2
Digital input signals0
Digital output signals0
Digital inputs parameterizableYes
Digital outputs parameterizableNo
3RK1301-0BB20-0AB4 — Electrical
ParameterValue
Rated value (DC)20.4 ... 28.8 V
Control supply voltage typeDC
Rated surge voltage6 kV
Adjustable Current Response Value Current Of The Current-Dependent Overload Release2.4 ... 8 A
Operating Voltage Rated Value200 ... 400 V
Number Of Poles For Main Current Circuit3
3RK1301-0BB20-0AB4 — Environmental
ParameterValue
Operating temperature range0 ... 60 °C
Storage temperature range-40 ... +70 °C
Shock resistance5g / 11 ms
Pollution degree3 at 400 V, 2 at 500 V according to IEC60664 (IEC61131)
3RK1301-0BB20-0AB4 — Mechanical
ParameterValue
Width65 mm
Depth150 mm
Height290 mm
Mounting methodpluggable on terminal module
3RK1301-0BB20-0AB4 — Specifications
ParameterValue
At 400 V rated value50 kA
At AC-3 at 400 V rated value8 A
Reverse StartingNo
Type Of The Motor Protectionsolid-state
Trip ClassCLASS 10 and 10A adjustable

Product details

The Siemens SIMATIC 3RK1301-0BB20-0AB4 is a direct motor starter designed for 24 V DC control supply (20.4 to 28.8 V DC permissible). It integrates PROFINET and PROFIBUS DP protocols, making it a networked component for distributed motor control in automation cells. The adjustable trip class (CLASS 10 and 10A) means it can be set to protect motor overloads with a faster or standard thermal curve — CLASS 10A is tighter for submersible or high-inertia loads where rapid trip is needed, while CLASS 10 covers standard induction motors. The 50 kA rated short-circuit current at 400 V gives substantial fault-clearing capacity without upstream fuses needing to coordinate down to a lower let-through.

Mounts vertically or horizontally, pluggable onto a terminal module. Dimensions: 290 mm height, 65 mm width, 150 mm depth. Operates at 0 to 60 °C ambient, storage and transport range -40 to +70 °C. Shock rated 5g / 11 ms, vibration 2g. Pollution degree 3 at 400 V, 2 at 500 V per IEC 60664 / IEC 61131 — suitable for industrial control panels with moderate conductive dust or humidity.

Provides 2 bytes of inputs and 2 bytes of outputs. Two digital inputs are available via the control module. No onboard digital outputs for brake control.

Frequently asked questions

What trip classes are available on this starter?

The adjustable trip class covers CLASS 10 and CLASS 10A. CLASS 10A provides a faster thermal curve for applications like submersible pumps or high-inertia loads.

MPN
3RK1301-0BB20-0AB4