Skip to main content
Siemens 3RK1301-0CB00-0AA2 — Remote I/O & Fieldbus Modules

Siemens SIMATIC 3RK1301-0CB00-0AA2 Motor Starter, CLASS 10,

MPN3RK1301-0CB00-0AA2

Siemens SIMATIC motor starter, direct starter, 24 V DC, CLASS 10, 50 kA at 400 V, PROFINET and PROFIBUS DP, 45 x 265 x 120 mm.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RK1301-0CB00-0AA2 — Identification
ParameterValue
Product designationMotor starters
Product designdirect starter
3RK1301-0CB00-0AA2 — Communication
ParameterValue
PROFIBUS DP supportYes
PROFINET supportYes
AS-Interface supportNo
Bus communicationYes
3RK1301-0CB00-0AA2 — I/O
ParameterValue
Digital inputs0
Digital input signals0
Digital output signals0
Digital inputs parameterizableNo
Digital outputs parameterizableNo
3RK1301-0CB00-0AA2 — Electrical
ParameterValue
Rated value (DC)20.4 ... 28.8 V
Control supply voltage typeDC
Rated surge voltage6 kV
Adjustable Current Response Value Current Of The Current-Dependent Overload Release0.18 ... 0.25 A
Operating Voltage Rated Value200 ... 400 V
Number Of Poles For Main Current Circuit3
3RK1301-0CB00-0AA2 — Environmental
ParameterValue
Operating temperature range0 ... 60 °C
Storage temperature range-40 ... +70 °C
Shock resistance5g / 11 ms
Pollution degree3 at 400 V, 2 at 500 V according to IEC60664 (IEC61131)
3RK1301-0CB00-0AA2 — Mechanical
ParameterValue
Width45 mm
Depth120 mm
Height265 mm
Mounting methodpluggable on terminal module
3RK1301-0CB00-0AA2 — Specifications
ParameterValue
At 400 V rated value50 kA
At AC-3 at 400 V rated value0.25 A
Reverse StartingNo
Type Of The Motor Protectionbimetal
Trip ClassCLASS 10

Product details

What this SIMATIC direct starter carries

The Siemens SIMATIC 3RK1301-0CB00-0AA2 is a direct motor starter rated for CLASS 10 trip protection, meaning it clears a locked-rotor condition within 10 seconds at the motor's cold-start current — standard for general-purpose induction motors on conveyors, pumps, and fans where quick overload clearance prevents winding damage. It's fed by a 24 V DC control supply (20.4 to 28.8 V tolerance) and handles a 50 kA prospective short-circuit current at 400 V, which is the SCCR the panel designer needs when coordinating upstream breakers in a high-fault industrial distribution. The unit mounts pluggable onto a terminal module — no hardwiring the power base — so a swap on a live line takes minutes, not hours. It sits in a 45 x 265 x 120 mm footprint, vertical or horizontal, and the 5g / 11 ms shock rating tells you it survives the vibration on a press or a crusher without nuisance trips.

Network and I/O profile

Dual-protocol onboard: PROFINET and PROFIBUS DP, so it drops into either a new PN line or a legacy DP daisy-chain without a gateway. The I/O map gives you 1 byte of inputs and 1 byte of outputs — enough for start/stop, fault reset, and status feedback to the PLC. No onboard digital I/O terminals (0 digital inputs, 0 digital outputs); the control signals come through the bus coupler. If you need local pushbuttons or indicator lights, you add them via a separate control module on the same terminal base.

Rated for pollution degree 3 at 400 V and degree 2 at 500 V per IEC 60664 / IEC 61131 — that's the standard for industrial enclosures where conductive dust or condensation is present. The product carries the SIMATIC brand and is designated as a motor starter.

Frequently asked questions

What is the depth and width of 3RK1301-0CB00-0AA2?

The depth is 120 mm and the width is 45 mm. Height is 265 mm. It mounts pluggable on a terminal module.

What network protocols does 3RK1301-0CB00-0AA2 support?

PROFINET and PROFIBUS DP are both onboard. The I/O map provides 1 byte of inputs and 1 byte of outputs over the fieldbus.

MPN
3RK1301-0CB00-0AA2