Skip to main content
Siemens 3RK1301-0CB10-0AA4 — Remote I/O & Fieldbus Modules

Siemens 3RK1301-0CB10-0AA4 SIMATIC Motor Starter, 24 V DC, P

MPN3RK1301-0CB10-0AA4

Siemens SIMATIC motor starter, 3RK1301-0CB10-0AA4, direct starter, 24 V DC, PROFINET + PROFIBUS DP, adjustable trip class 10 and 20, 50 kA at 400 V, pluggable on terminal module.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RK1301-0CB10-0AA4 — Identification
ParameterValue
Product designationMotor starters
Product designdirect starter
3RK1301-0CB10-0AA4 — Communication
ParameterValue
PROFIBUS DP supportYes
PROFINET supportYes
AS-Interface supportNo
Bus communicationYes
3RK1301-0CB10-0AA4 — I/O
ParameterValue
Digital inputs2
Digital input signals0
Digital output signals0
Digital inputs parameterizableYes
Digital outputs parameterizableNo
3RK1301-0CB10-0AA4 — Electrical
ParameterValue
Rated value (DC)20.4 ... 28.8 V
Control supply voltage typeDC
Rated surge voltage6 kV
Adjustable Current Response Value Current Of The Current-Dependent Overload Release2.4 ... 16 A
Operating Voltage Rated Value200 ... 400 V
Number Of Poles For Main Current Circuit3
3RK1301-0CB10-0AA4 — Environmental
ParameterValue
Operating temperature range0 ... 60 °C
Storage temperature range-40 ... +70 °C
Shock resistance5g / 11 ms
Pollution degree3 at 400 V, 2 at 500 V according to IEC60664 (IEC61131)
3RK1301-0CB10-0AA4 — Mechanical
ParameterValue
Width65 mm
Depth150 mm
Height290 mm
Mounting methodpluggable on terminal module
3RK1301-0CB10-0AA4 — Specifications
ParameterValue
At 400 V rated value50 kA
Reverse StartingNo
Type Of The Motor Protectionsolid-state
Trip ClassCLASS 10 and 20 adjustable

Product details

The Siemens 3RK1301-0CB10-0AA4 is a SIMATIC-branded motor starter — a direct starter designed for 24 V DC control voltage, with PROFINET and PROFIBUS DP onboard. It's the kind of part you'd spec into a motor control center or a distributed automation cabinet where you need coordinated motor protection and fieldbus integration in one package. The adjustable trip class (CLASS 10 and 20) means you can match the overload curve to the motor's starting profile — CLASS 10 for faster-starting loads like pumps and fans, CLASS 20 for higher-inertia loads like conveyors or crushers that take longer to spin up. That adjustability saves stocking a separate overload relay for each application. Pollution degree 3 at 400 V per IEC 60664 means it's rated for the conductive-dust and humidity conditions typical of industrial enclosures.

Footprint is 65 mm wide by 290 mm tall by 150 mm deep. Mounting position is vertical or horizontal. Fastening is pluggable on a terminal module — the power and control wiring lands on a fixed base, and the starter module itself clips on top. That means you can swap the electronics without pulling wires, which cuts downtime during a replacement.

Shock rated at 5g for 11 ms, vibration at 2g.

Frequently asked questions

What trip classes does this motor starter support?

Adjustable between CLASS 10 and CLASS 20. CLASS 10 suits standard motor starts (pumps, fans), CLASS 20 handles higher-inertia loads (conveyors, crushers).

What fieldbus protocols are supported?

PROFINET and PROFIBUS DP are both onboard. No separate communication module needed.

MPN
3RK1301-0CB10-0AA4