Skip to main content
Siemens 3RK1301-0JB00-1AA2 — Remote I/O & Fieldbus Modules

Siemens 3RK1301-0JB00-1AA2 SIMATIC Motor Starter, Reversing

MPN3RK1301-0JB00-1AA2

Siemens SIMATIC 3RK1301-0JB00-1AA2 reversing motor starter, PROFINET + PROFIBUS DP, CLASS 10 trip, 50 kA SCCR at 400 V, pluggable on terminal module, 24 V DC.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RK1301-0JB00-1AA2 — Identification
ParameterValue
Product designationMotor starters
Product designreversing starter

Communication

3RK1301-0JB00-1AA2 — Communication
ParameterValue
PROFIBUS DP supportYes
PROFINET supportYes
AS-Interface supportNo
Bus communicationYes

I/O

3RK1301-0JB00-1AA2 — I/O
ParameterValue
Digital inputs0
Digital input signals0
Digital output signals0
Digital inputs parameterizableNo
Digital outputs parameterizableNo

Electrical

3RK1301-0JB00-1AA2 — Electrical
ParameterValue
Rated value (DC)20.4 ... 28.8 V
Control supply voltage typeDC
Rated surge voltage6 kV
Adjustable Current Response Value Current Of The Current-Dependent Overload Release0.7 ... 1 A
Operating Voltage Rated Value200 ... 400 V
Number Of Poles For Main Current Circuit3

Environmental

3RK1301-0JB00-1AA2 — Environmental
ParameterValue
Operating temperature range0 ... 60 °C
Storage temperature range-40 ... +70 °C
Shock resistance5g / 11 ms
Pollution degree3 at 400 V, 2 at 500 V according to IEC60664 (IEC61131)

Mechanical

3RK1301-0JB00-1AA2 — Mechanical
ParameterValue
Width90 mm
Depth120 mm
Height265 mm
Mounting methodpluggable on terminal module

Specifications

3RK1301-0JB00-1AA2 — Specifications
ParameterValue
At 400 V rated value50 kA
At AC-3 at 400 V rated value1 A
Reverse StartingYes
Type Of The Motor Protectionbimetal
Trip ClassCLASS 10

Product details

Reversing starter with PROFINET and PROFIBUS DP

The 3RK1301-0JB00-1AA2 is a SIMATIC motor starter configured as a reversing starter — it controls motor direction forward and reverse without external contactors. It supports both PROFINET and PROFIBUS DP protocols, so it drops into either fieldbus architecture without a gateway. Rated short-circuit current is 50 kA at 400 V, giving the panel builder headroom for high-fault installations without cascading upstream breakers.

Panel fit and supply voltage tolerance

Dimensions are 120 mm deep, 90 mm wide, 265 mm tall — fits standard control-panel backplanes. Mounting position is vertical or horizontal, with pluggable attachment onto a terminal module for quick swap without rewiring the field cables. Vibration resistance is 2g, shock resistance 5g / 11 ms — rated for machine-mounted cabinets.

MPN
3RK1301-0JB00-1AA2