Siemens 3RK1315-6KS41-0AA0

Siemens 3RK1315-6KS41-0AA0 SIRIUS Motor Starter

MPN 3RK1315-6KS41-0AA0
NRND

Siemens SIRIUS 3RK1315-6KS41-0AA0 direct motor starter, AS-Interface, 4 digital inputs, CLASS 10, IP65, 24 VDC, 159 x 294 x 215 mm.

$350.52 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RK1315-6KS41-0AA0 specifications
ParameterValue
IP ratingIP65
Mountingscrew fixing
Depth159 mm
Width294 mm
Height215 mm
Trip classCLASS 10

Product details

Active SIRIUS direct starter with AS-Interface

The 3RK1315-6KS41-0AA0: Rated for 0.75 kW at 400 V and 0.7 hp at 460/480 V, it handles small three-phase motor loads in a single enclosure rated IP65 for washdown environments.

AS-Interface bus node with integrated I/O

This unit communicates via AS-Interface protocol (no PROFIBUS or PROFINET onboard) and provides 4 digital inputs addressed through an M12 plug — the fieldbus connection and sensor wiring terminate at the same IP65 enclosure. Supply voltage is 24 VDC nominal, with a permissible range of 20.4 to 28.8 V and an absolute maximum of 31.6 V — the onboard electronics regulate the bus power for the AS-i segment.

CLASS 10 trip curve and mounting flexibility

The CLASS 10 trip characteristic means the overload relay opens within 10 seconds at 7.2× rated current — standard for protecting standard induction motors during locked-rotor conditions. Mounting is via screw fixing in any orientation (vertical, horizontal, flat), though the recommended position is horizontal for optimal heat dissipation. The enclosure measures 159 mm deep × 294 mm wide × 215 mm tall.

Environmental ratings for industrial floors

IP65 protection means the enclosure is dust-tight and protected against low-pressure water jets — suitable for installation directly on machinery without a separate cabinet. Operating temperature range is -25 to +55 °C; storage and transport tolerate -40 to +70 °C. Vibration resistance is 7 mm / 2g, shock resistance 12g / 11 ms — the unit survives typical conveyor and pump vibration without loosening screw terminals.

MPN