Skip to main content
Siemens 3RK1322-0CS02-0AA3 — Remote I/O & Fieldbus Modules

Siemens 3RK1322-0CS02-0AA3 AS-i Compact Starter, 0.18-0.25 A

MPN3RK1322-0CS02-0AA3

Siemens SIRIUS AS-i compact starter, electromechanical DOL starter, setting range 0.18…0.25 A, AC-3 0.06 kW at 400 V, IP65, with integrated brake contact and 2 inputs.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RK1322-0CS02-0AA3 — Identification
ParameterValue
Product designdirect starter
3RK1322-0CS02-0AA3 — Communication
ParameterValue
PROFIBUS DP supportNo
AS-Interface supportYes
Bus communicationYes
3RK1322-0CS02-0AA3 — Electrical
ParameterValue
Voltage typeDC
3RK1322-0CS02-0AA3 — Environmental
ParameterValue
Ingress protection (IP)IP65
Ambient operating temperature-25 ... +55 °C
3RK1322-0CS02-0AA3 — Mechanical
ParameterValue
Width120 mm
Depth190 mm
Height270 mm
3RK1322-0CS02-0AA3 — Specifications
ParameterValue
Type Of The Motor Protectionbimetal

Product details

The Siemens 3RK1322-0CS02-0AA3 is an AS-interface compact direct starter — an electromechanical DOL (direct-on-line) motor starter in an IP65-rated enclosure, ready for field-mounting near the motor rather than inside a control cabinet. It switches a 0.06 kW motor at 400 V under AC-3 duty (the standard induction-motor switching category per IEC 60947-4-1), with a setting range of 0.18 to 0.25 A via a bimetal overload relay. The unit includes a motor brake output (400 V AC) and two integrated inputs, so it can handle a small brake motor and accept local sensor signals without an extra I/O block.

AS-interface integration and connectivity

Communication runs over AS-interface (AS-i protocol), not PROFIBUS DP. That keeps wiring simple — a single two-wire flat cable carries both power and data to the starter. The main current circuit connects via tab terminals, and the motor outgoing feeder and power connection are both 9-pole, so the cabling is a single pre-wired harness to the motor and the AS-i network. The unit is designed for direct panel-side or machine-frame mounting — no DIN rail required. Dimensions are 270 mm high, 120 mm wide, 190 mm deep. At IP65, you can mount it directly on the machine frame without a separate enclosure, saving panel space and gland-plate work.

Protection and breaking capacity

Short-circuit protection is provided by circuit-breakers integrated into the design, with a maximum short-circuit breaking capacity (Icu) of 50,000 A at 400 V. That is a high fault-current rating for a starter this size — it can sit on a high-capacity distribution board without needing upstream fuses to limit the let-through. The motor protection is bimetal-based, set within the 0.18 to 0.25 A window. The ambient temperature range during operation is -25 to +55 °C, which covers most plant-floor conditions without derating. The equipment marking per DIN EN 61346-2 is Q (motor starter function).

Frequently asked questions

Where can I buy 3RK1322-0CS02-0AA3 and what is the price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the setting range and motor rating of 3RK1322-0CS02-0AA3?

The setting range is 0.18 to 0.25 A, and the motor rating is 0.06 kW at 400 V under AC-3 duty.

What is the IP rating and enclosure size of this AS-i starter?

IP65 rated. Dimensions are 270 mm high, 120 mm wide, 190 mm deep.

Will 3RK1322-0CS02-0AA3 drop into a panel specified around 3RT5065-6AB36 without rewiring?

No — the 3RT5065-6AB36 is a SIRIUS power contactor (S10 size, 330 A at 40 °C) with screw terminals, designed for cabinet mounting. The 3RK1322-0CS02-0AA3 is a compact AS-i starter rated 0.25 A with tab terminals and an IP65 field-mount enclosure. They are not footprint-compatible and serve different current ranges and wiring schemes.

MPN
3RK1322-0CS02-0AA3