Skip to main content
Siemens 3RK1322-0ES02-0AA0 — Remote I/O & Fieldbus Modules

Siemens 3RK1322-0ES02-0AA0 AS-i Compact Starter, 0.28-0.4 A,

MPN3RK1322-0ES02-0AA0

Siemens SIRIUS 3RK1322-0ES02-0AA0, AS-i compact direct starter, IP65, electromechanical DOL, setting range 0.28…0.4 A, AC-3 0.1 kW / 400 V, with 2 integrated inputs, 9-pole motor and power connections.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RK1322-0ES02-0AA0 — Identification
ParameterValue
Product designdirect starter
3RK1322-0ES02-0AA0 — Communication
ParameterValue
PROFIBUS DP supportNo
AS-Interface supportYes
Bus communicationYes
3RK1322-0ES02-0AA0 — Electrical
ParameterValue
Voltage typeDC
3RK1322-0ES02-0AA0 — Environmental
ParameterValue
Ingress protection (IP)IP65
Ambient operating temperature-25 ... +55 °C
3RK1322-0ES02-0AA0 — Mechanical
ParameterValue
Width120 mm
Depth190 mm
Height270 mm
3RK1322-0ES02-0AA0 — Specifications
ParameterValue
Type Of The Motor Protectionbimetal

Product details

What this AS-i compact starter does on the line

The Siemens 3RK1322-0ES02-0AA0 is an AS-interface compact direct starter (DOL) in an IP65 enclosure, rated for 0.1 kW at 400 V AC-3 duty with a setting range of 0.28 to 0.4 A. It uses a bimetal overload relay for motor protection and electromechanical switching contacts, with short-circuit protection provided by circuit-breakers.

Fieldbus integration and I/O

Communication runs on AS-interface protocol, not PROFIBUS DP — verify your network master supports AS-i before specifying. The starter includes two integrated inputs for local sensors (e.g., limit switches or presence detectors) and a bus communication function, so it can report motor status and accept start/stop commands over the same two-wire AS-i cable. The 9-pole motor outgoing feeder and 9-pole power connection use tab terminals; plan for the correct mating connectors at the machine end.

Short-circuit withstand and coordination

The maximum short-circuit breaking capacity (Icu) at 400 V is rated at 50 000 A — that is the fault current this starter can safely interrupt without catastrophic failure.

Environmental limits and mounting

Rated for ambient operation from -25 °C to +55 °C, which covers unheated plant areas and warm machine zones. The IP65 enclosure allows direct mounting on the machine without a separate panel; cable entries need IP65-rated glands.

Frequently asked questions

What is the setting range and motor power for 3RK1322-0ES02-0AA0?

The setting range is 0.28 to 0.4 A, and the rated operating power at AC-3, 400 V is 0.1 kW.

Where can I buy 3RK1322-0ES02-0AA0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

Does 3RK1322-0ES02-0AA0 use PROFIBUS or AS-interface?

It uses AS-interface protocol for communication; PROFIBUS DP is not supported on this variant.

What is the short-circuit breaking capacity of this starter at 400 V?

The maximum short-circuit breaking capacity (Icu) at 400 V is 50 000 A.

MPN
3RK1322-0ES02-0AA0