Skip to main content
Siemens 3RK1322-1CS02-0AA0 — Remote I/O & Fieldbus Modules

Siemens 3RK1322-1CS02-0AA0 AS-i Compact Starter, 1.8-2.5 A,

MPN3RK1322-1CS02-0AA0

Siemens 3RK1322-1CS02-0AA0, AS-i compact direct starter, electromechanical DOL, setting range 1.8-2.5 A, 0.9 kW / 400 V AC-3, IP65, with 2 integrated inputs.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RK1322-1CS02-0AA0 — Identification
ParameterValue
Product designdirect starter
3RK1322-1CS02-0AA0 — Communication
ParameterValue
PROFIBUS DP supportNo
AS-Interface supportYes
Bus communicationYes
3RK1322-1CS02-0AA0 — Electrical
ParameterValue
Voltage typeDC
3RK1322-1CS02-0AA0 — Environmental
ParameterValue
Ingress protection (IP)IP65
Ambient operating temperature-25 ... +55 °C
3RK1322-1CS02-0AA0 — Mechanical
ParameterValue
Width120 mm
Depth190 mm
Height270 mm
3RK1322-1CS02-0AA0 — Specifications
ParameterValue
Type Of The Motor Protectionbimetal

Product details

The Siemens 3RK1322-1CS02-0AA0 is an AS-i compact direct starter — a fully enclosed, IP65-rated motor starting unit that combines a contactor, bimetal overload relay, and short-circuit protection into one field-mounted package. It's designed for distributed motor control on AS-Interface networks, eliminating the need for a central control panel for small motor branches. Rated for 0.9 kW at 400 V AC-3 duty, the setting range covers 1.8 to 2.5 A, making it suitable for small three-phase motors like those driving conveyors, fans, or pumps in decentralized layouts.

The 1.8–2.5 A setting range matches the full-load current of a 0.75–0.9 kW motor at 400 V; the bimetal overload tracks motor heating directly, so you set it to the motor nameplate FLA. Tab terminals for the main circuit mean you need mating 6.3 mm fast-on receptacles — not screw clamps. The 9-pole motor and power connectors are pre-wired; the two integrated inputs let you connect local sensors (e.g., limit switches or emergency stops) directly into the AS-i node without extra I/O blocks.

Integration notes

The 190 mm depth, 120 mm width, and 270 mm height (–) define the envelope for machine-mounted installation. It's not a DIN-rail device — it bolts directly to a mounting plate or machine frame. The AS-i bus connection uses the standard yellow flat cable; the two integrated inputs are M12, typically for PNP sensors. No PROFIBUS DP onboard — this is strictly AS-Interface. If your network is PROFIBUS, you'd need a gateway. The motor brake output is absent, so separate brake control is required for holding-brake motors.

Frequently asked questions

What are the key ratings I need to check for fit?

The motor rating is 0.9 kW at 400 V AC-3, with an overload setting range of 1.8 to 2.5 A. The short-circuit breaking capacity is 50 kA at 400 V. The enclosure is IP65, and it communicates via AS-Interface only.

What is the physical size of this starter?

The dimensions are 190 mm deep, 120 mm wide, and 270 mm high. It is a field-mounted unit, not a DIN-rail device.