Skip to main content
Siemens 3RK1322-1CS02-1AA0 — Remote I/O & Fieldbus Modules

Siemens 3RK1322-1CS02-1AA0 AS-i Reversing Starter, 0.9 kW, I

MPN3RK1322-1CS02-1AA0

Siemens AS-i compact reversing starter, electromechanical, IP65, 1.8-2.5 A setting range, 0.9 kW at 400 V AC-3, 50 kA breaking capacity.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RK1322-1CS02-1AA0 — Identification
ParameterValue
Product designreversing starter
3RK1322-1CS02-1AA0 — Communication
ParameterValue
PROFIBUS DP supportNo
AS-Interface supportYes
Bus communicationYes
3RK1322-1CS02-1AA0 — Electrical
ParameterValue
Voltage typeDC
3RK1322-1CS02-1AA0 — Environmental
ParameterValue
Ingress protection (IP)IP65
Ambient operating temperature-25 ... +55 °C
3RK1322-1CS02-1AA0 — Mechanical
ParameterValue
Width120 mm
Depth190 mm
Height270 mm
3RK1322-1CS02-1AA0 — Specifications
ParameterValue
Type Of The Motor Protectionbimetal

Product details

The Siemens 3RK1322-1CS02-1AA0 is an AS-Interface compact reversing starter designed for distributed motor control in washdown or dusty environments. It integrates an electromechanical contactor with bimetal overload protection, short-circuit protection via circuit-breakers, and two integrated inputs — all in an IP65-rated enclosure ready for direct machine-mounting without a separate panel.

The setting range of 1.8 to 2.5 A means the bimetal overload relay is factory-set for that window; if your motor's FLA falls outside it, you need a different starter variant.

This is a reversing starter — it switches motor direction via two contactors mechanically interlocked, so no external reversing contactor or interlock wiring is needed. The 9-pole motor outgoing feeder and 9-pole power connection use tab terminals; expect to crimp fast-on connectors, not screw-clamp terminals. AS-Interface protocol is built in (no PROFIBUS DP option here), so it communicates over a two-wire AS-i cable carrying both power and data. The two integrated inputs can take limit switches or proximity sensors directly, reducing junction-box wiring. Mounts directly on the machine frame via the IP65 housing; no DIN rail required.

Frequently asked questions

Does this starter support PROFIBUS DP communication?

No, the 3RK1322-1CS02-1AA0 supports AS-Interface protocol only. PROFIBUS DP is not available on this variant. If you need PROFIBUS, look at the 3RK1322 series variants with DP designation.

What is the operating temperature range for this device?

The ambient temperature during operation is -25 to +55 °C. This covers most industrial environments, but sustained full-load operation at the upper end may require derating per Siemens application guidelines.

MPN