Siemens 3RK1325-6KS41-1AA3 — Remote I/O & Fieldbus Modules

Siemens 3RK1325-6KS41-1AA3 SIRIUS Reversing Starter, 0.75 kW

MPN3RK1325-6KS41-1AA3
NRND

Siemens SIRIUS 3RK1325-6KS41-1AA3 reversing motor starter, 0.75 kW at 400 V, IP65, 4 digital inputs, trip class selectable 5/10/15/20, screw fixing, 159 x 294 x 215 mm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RK1325-6KS41-1AA3 — Identification
ParameterValue
Product designationMotor starters
Product designreversing starter
3RK1325-6KS41-1AA3 — Communication
ParameterValue
PROFIBUS DP supportNo
PROFINET supportNo
AS-Interface supportYes
AS-Interface supportYes
Bus communicationYes
3RK1325-6KS41-1AA3 — I/O
ParameterValue
Digital inputs4
Digital input signals4
Digital output signals1
Digital inputs parameterizableYes
Digital outputs parameterizableYes
3RK1325-6KS41-1AA3 — Electrical
ParameterValue
Rated value (DC)20.4 ... 28.8 V
Control supply voltage typeDC
Rated surge voltage6 000 V
Adjustable Current Response Value Current Of The Current-Dependent Overload Release0.15 ... 2 A
Operating Voltage Rated Value200 ... 440 V
Number Of Poles For Main Current Circuit3
3RK1325-6KS41-1AA3 — Environmental
ParameterValue
Ingress protection (IP)IP65
Operating temperature range-25 ... +55 °C
Storage temperature range-40 ... +70 °C
Shock resistance12g / 11 ms
Pollution degree3
3RK1325-6KS41-1AA3 — Mechanical
ParameterValue
Width294 mm
Depth159 mm
Height215 mm
Mounting methodscrew fixing
3RK1325-6KS41-1AA3 — Specifications
ParameterValue
At 400 V rated value0.75 kW
At AC-3 at 400 V rated value2 A
Reverse StartingYes
Type Of The Motor Protectionfull motor protection
Trip ClassCLASS 5, 10, 15, 20

Product details

What this reversing starter does differently

The 3RK1325-6KS41-1AA3 is a SIRIUS reversing starter that packs forward/reverse motor control, overload protection, and four digital inputs into a single IP65 enclosure — no separate contactor pair needed for reversing duty. Rated 0.75 kW at 400 V (0.7 hp at 460/480 V, 1 hp at 575/600 V), it covers the typical small conveyor, pump, or actuator reversing job. Supply voltage is 24 V DC nominal (20.4…28.8 V range, max 31.6 V), so it drops straight onto a standard industrial 24 V bus without a separate power supply module.

Panel fit and mounting constraints

Footprint is 159 mm deep by 294 mm wide by 215 mm tall — allow clearance for the M12 plug on device addressing and the HAN Q4/2 main-circuit connector. Screw fixing to the backplate; mounting position can be vertical, horizontal, or flat. IP65 rating means the housing is dust-tight and splash-proof — suitable for on-machine or floor-level mounting where washdown or debris is present, but not for submersion. Ambient operating range is -25 to +55 °C; storage and transport tolerance -40 to +70 °C. Shock rated 12g / 11 ms, vibration 7 mm / 2g — handles the typical conveyor or machine-tool environment.

Trip class and protection coordination

Trip class is selectable between 5, 10, 15, and 20 — match the thermal overload response to the motor's start-up profile. Class 10 is the default for standard induction motors; Class 20 buys extra time for high-inertia loads like fans or centrifuges. The starter supports reverse starting directly, so the reversing contactor pair is internal — no external reversing contactor or interlock wiring required. ON-delay is 85 ms, OFF-delay 65 ms — fast enough for most sequencing but not for safety-rated instant-off; plan your logic scan cycle accordingly.

Frequently asked questions

Where can I buy 3RK1325-6KS41-1AA3 and how do I get a price?

This part is sourced to order against your BOM through independent industrial distribution.

What is 3RK1325-6KS41-1AA3's trip class range?

Trip class is selectable between 5, 10, 15, and 20 — choose based on the motor's start-up current duration. Class 10 fits standard motors; Class 20 is for high-inertia loads.

MPN