Skip to main content
Siemens 3RK1395-6KS71-2AD5 — Remote I/O & Fieldbus Modules

Siemens 3RK1395-6KS71-2AD5 SIRIUS Motor Starter, IP65, 2A at

MPN3RK1395-6KS71-2AD5
NRND

Siemens SIRIUS motor starter, 3RK1395-6KS71-2AD5, direct starter design, IP65, 2 A at 400 V AC-3, 4 digital inputs, 2 digital outputs, HAN Q4/2 connector.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RK1395-6KS71-2AD5 — Identification
ParameterValue
Product designationMotor starters
Product designdirect starter
3RK1395-6KS71-2AD5 — Communication
ParameterValue
PROFIBUS DP supportNo
PROFINET supportNo
AS-Interface supportNo
AS-Interface supportNo
Bus communicationYes
3RK1395-6KS71-2AD5 — I/O
ParameterValue
Digital inputs4
Digital input signals4
Digital output signals2
Digital inputs parameterizableYes
Digital outputs parameterizableYes
3RK1395-6KS71-2AD5 — Electrical
ParameterValue
Rated value (DC)20.4 ... 28.8 V
Control supply voltage typeDC
Rated surge voltage6 000 V
Adjustable Current Response Value Current Of The Current-Dependent Overload Release0.15 ... 2 A
Operating Voltage Rated Value200 ... 440 V
Number Of Poles For Main Current Circuit3
3RK1395-6KS71-2AD5 — Environmental
ParameterValue
Ingress protection (IP)IP65
Operating temperature range-25 ... +55 °C
Storage temperature range-40 ... +70 °C
Shock resistance12g / 11 ms
Pollution degree3
3RK1395-6KS71-2AD5 — Mechanical
ParameterValue
Width294 mm
Depth148 mm
Height215 mm
Mounting methodscrew fixing
3RK1395-6KS71-2AD5 — Specifications
ParameterValue
At 400 V rated value0.75 kW
At AC-3 at 400 V rated value2 A
Reverse StartingNo
Type Of The Motor Protectionfull motor protection
Trip ClassCLASS 5, 10, 15, 20

Product details

SIRIUS direct starter for distributed motor control

The Siemens SIRIUS 3RK1395-6KS71-2AD5 is a direct-on-line motor starter in an IP65 housing, rated for 2 A at 400 V AC-3 duty — sufficient for a 0.75 kW motor at 400 V or 0.7 hp at 480 V. The 24 V DC supply (20.4…28.8 V range) powers the coil and onboard logic. The HAN Q4/2 connector (ISO 23570) provides a standardized power interface, simplifying field wiring and replacement.

Trip class flexibility and thermal management

The overload relay supports selectable Trip Classes 5, 10, 15, and 20, covering fast-acting protection for short-time overloads (Class 5) through slower curves for high-inertia loads (Class 20). This flexibility lets the starter match the motor's thermal time constant without swapping hardware. Operating temperature range is -25…+55 °C, with storage/transport tolerance from -40…+70 °C. Shock resistance is 12 g for 11 ms; vibration resistance is 7 mm at 2 g.

I/O and control interface

The starter provides 4 digital inputs and 2 digital outputs for local control and status feedback. ON-delay is 25 ms, OFF-delay 35 ms. No PROFINET, PROFIBUS DP, or AS-Interface protocol is onboard — this is a standalone unit intended for hardwired or remote I/O control via the digital inputs. Mounting is via screw fixing, and the unit can be installed vertically, horizontally, or flat. Horizontal orientation is recommended for optimal heat dissipation. The 294 mm width, 215 mm height, and 148 mm depth define the panel footprint.

Frequently asked questions

What is the depth of 3RK1395-6KS71-2AD5?

The depth is 148 mm. Overall dimensions are 294 mm wide × 215 mm high × 148 mm deep.

MPN