Skip to main content
Siemens 3RK1400-0CE00-0TB3 — Remote I/O & Fieldbus Modules

Siemens 3RK1400-0CE00-0TB3 AS-Interface Module, 4I/4O

MPN3RK1400-0CE00-0TB3

Siemens 3RK1400-0CE00-0TB3 AS-Interface module, 4 digital inputs PNP, 4 digital outputs 45 mA, screw terminal, 24 V DC output supply via AS-i cable.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Product details

AS-Interface Module for Discrete I/O on the AS-i Bus

The Siemens 3RK1400-0CE00-0TB3 is an AS-Interface module providing 4 PNP inputs and 4 outputs rated at 45 mA each, with screw terminal connections. Output supply is drawn directly from the AS-i cable at 24 V DC, eliminating a separate power feed for the output stage. This module is designed for the TUCHENHAGEN form factor, a compact housing common in automotive and material-handling AS-i drops.

The 4 PNP inputs are suitable for sourcing-type sensors (e.g., proximity, photoelectric) common on AS-i networks. The 4 outputs at 45 mA each handle small loads such as indicator lamps, solenoid pilot valves, or signal relays — not direct motor or actuator power. Outputs are supplied at 24 V DC via the AS-i yellow cable, which simplifies wiring but limits total output current to what the AS-i segment power supply can deliver. On a standard AS-i power supply (typically 2 A or 4 A), four outputs at 45 mA is well within budget, but if the same segment also powers other modules, the aggregate draw needs checking. The screw terminal connection is field-friendly for maintenance electricians who prefer a screwdriver over a spring-cage tool. It accepts standard ferruled or solid conductors. The TUCHENHAGEN housing is a specific mechanical footprint — verify that the mounting base or profile rail in your panel matches this form factor before ordering.

Deployment Context

This module mounts on an AS-i flat-cable profile rail or a standard DIN rail via an adapter base. It is typically deployed in a control cabinet or junction box near the field devices it serves, reducing home-run wiring back to the PLC. The 24 V DC output supply via the AS-i cable means no additional 24 V DC distribution is needed at the module — the yellow AS-i cable carries both data and power for the outputs.

Frequently asked questions

What does the description '4 I/4 O with screw terminal' mean for wiring?

It means 4 PNP inputs and 4 outputs at 45 mA each, all connected via screw terminals. Output power is supplied through the AS-i cable at 24 V DC, so no separate output supply wiring is needed.

MPN