Specifications

3RK1400-0GQ20-0AA3 — Identification
ParameterValue
Product designdigital I/O modules for operation in the field, IP65 - K45
3RK1400-0GQ20-0AA3 — I/O
ParameterValue
Digital inputs2
3RK1400-0GQ20-0AA3 — Environmental
ParameterValue
Ingress protection (IP)IP67
Operating temperature range-25 ... +85 °C
Storage temperature range-40 ... +85 °C
Shock resistance15g / 11 ms
3RK1400-0GQ20-0AA3 — Mechanical
ParameterValue
Width45 mm
Depth30 mm
Height80 mm
Mounting methodstandard rail mounting/wall mounting using mounting plate for K45 compact module

Product details

The Siemens 3RK1400-0GQ20-0AA3 is a K45 compact field I/O module that gives you two PNP digital inputs and two PNP digital outputs in a single IP67 housing — no control cabinet needed for the I/O points themselves. It's built for the ET 200pro distributed I/O family, meaning it sits directly on the machine frame or conveyor line, wired via standard M12 connectors.

The 0.2 A limit — what it means on the line

The module's total current budget across all inputs and outputs is 0.2 A. That's not per channel — it's the whole module. Plan your load split accordingly; the built-in short-circuit protection will trip if you exceed it.

Field mounting and connectivity

Rated IP67, so it handles washdown and wet environments on the plant floor — common for automotive, food-and-bev, or material-handling zones where you don't want I/O pulled back to a cabinet. Mounts via standard rail or wall plate. The two M12 sockets carry the I/O: socket 1 maps PIN 4 to input D0 and PIN 2 to output D3; socket 2 maps PIN 4 to input D1 and PIN 2 to output D4. PIN 5 on each socket is the ground terminal, routed out through a 2.8 x 0.8 mm flat tab sleeve for panel bonding.

Frequently asked questions

What does the 2 x (1 input / 1 output) type mean?

It means the module has two M12 sockets, each carrying one PNP digital input and one PNP digital output — so two inputs and two outputs total. Inputs are on PIN 4 of each socket; outputs on PIN 2.

MPN